Private wells · sizing

    What size pressure tank does your well need?

    Tank sizing turns on two numbers you already own: the pump's gallons per minute and the cut-in pressure on the switch. Here is the arithmetic the charts skip, and the settings that change the answer.

    30-second answer

    A pressure tank is sized from two numbers you already own: your pump's output in gallons per minute, and the cut-in pressure on the switch. Michigan's state well manual sizes a domestic tank so that a pump delivering 10 to 20 gallons per minute runs for at least one full minute per cycle, and that run time is what sets the volume the tank has to hold Source 1: State of Michigan Water Well Manual.

    That volume is called drawdown, and it is a fraction of the number on the label. A pre-charged bladder tank at 30/50 psi gives up about 25 percent of its total volume as usable water; a plain steel tank with no pre-charge at the same settings gives about 10 percent Source 1: State of Michigan Water Well Manual. So a 40-gallon tank is not 40 gallons of anything. Work out the drawdown you need, then find the nameplate that delivers it at the settings you actually run.

    DIY with cautions

    What the number on the label is not

    A pressure tank is a buffer. The Texas Well Owner Network describes the job in one line: most home well systems have a pressurized storage tank so that small demands do not continually activate the pump Source 4: Texas Well Owner Network, Well Owner's Guide to Water Supply. Everything on this page follows from how much water that buffer hands you between pump starts.

    Washington's design manual gives the quantity its engineering name: withdrawal capacity is the portion of tank volume that can be usefully withdrawn between pumping cycles while still maintaining 30 psi throughout the house under peak demand Source 2: Washington State Water System Design Manual, DOH 331-123. The everyday word is drawdown. The second half of that definition is the half that matters. Water that leaves the tank after the pressure has already collapsed is not capacity. By then, the pump has restarted.

    Three tanks, three fractions, same physical volume. Michigan puts numbers on it.

    • A bladder or diaphragm tank with a correct pre-charge, running at 30 to 50 psi, makes about 25 percent of its total volume available.
    • A plain steel tank with a pre-charge, holding its high water level at 55 percent of capacity, makes about 20 percent.
    • A plain steel tank with no pre-charge at all makes about 10 percent Source 1: State of Michigan Water Well Manual.

    The tank has not changed size between those three lines. What changed is how much air is in it and where the air is kept.

    Infographic of well pressure tank sizing. A cutaway tank at grade beside a well shows a compressed air chamber above a membrane and water below it, over three panels: usable water at 25, 20 and 10 percent of tank volume by tank type; minimum pump run times of 1 to 4 minutes by pump output; and the two pre-charge figures, 2 psi below cut-in for normal operation and 5 psi for extra supply at peak demand
    Drawdown, run time and pre-charge, all stated in the text above. Michigan Water Well Construction Manual, accessed July 2026.

    This is the conversion the sizing charts skip. It runs in the direction you need, not the direction a catalogue runs. You do not start from a tank and ask what it gives; you start from the drawdown you need and divide.

    Twenty-eight gallons from a pre-charged bladder tank is 28 divided by 0.25, a 112-gallon nameplate. The same 28 gallons from an unpre-charged steel tank is 280.

    Michigan does that division in its own worked example and lands on a 200-gallon tank for a 50-gallon requirement Source 1: State of Michigan Water Well Manual.

    One boundary before the arithmetic starts. This page sizes a tank on plan. It does not diagnose one that is misbehaving.

    A pump restarting every few seconds, water spraying from the air valve, or a waterlogged tank is a different question, with a different order of checks. See the short-cycling guide, which also carries the dated cost of every repair named here.

    There are two sizing rules, and which one applies depends on your well

    Most homeowner guides that size a tank at all use one rule. Michigan uses two, and the fork between them is whether the pump can meet the house's peak demand on its own Source 1: State of Michigan Water Well Manual. Getting the fork wrong turns a correct formula into a tank too small for the house it was bought for.

    First, the fixture count. Michigan's shortcut for pump capacity is that the minimum output in gallons per minute should equal the number of water-using fixtures in the house. Its own example counts two bathrooms, a kitchen sink, a disposal, a dishwasher, a washing machine, a laundry sink and three hose bibs, reaches 14 fixtures, and calls for a 14-gallon-per-minute pump Source 1: State of Michigan Water Well Manual. Count yours before reading further, because the fork depends on it.

    Rule A, pump protection. This is the rule when the pump meets or exceeds peak demand. Drawdown equals the pump's output multiplied by a minimum run time, and Michigan tabulates the run time by pump size where the manufacturer states none: one minute for 10 to 20 gallons per minute, two for 21 to 50, three for 51 to 75, and four for 76 to 100 Source 1: State of Michigan Water Well Manual.

    Larger pumps get longer run times because starting them draws more electrical energy. A 14-gallon-per-minute pump on a one-minute cycle needs 14 gallons of drawdown, and 28 if you want a two-minute cycle.

    Rule B, peak demand. This is the rule when the pump cannot keep up. It produces a larger tank. Michigan gives the seven-minute peak demand by bathroom count, with the pump size that meets it unaided: 1 bathroom, 45 gallons, 7 gpm; 1.5, 70 gallons, 10 gpm; 2 to 2.5, 98 gallons, 14 gpm; 3 to 4, 122 gallons, 17 gpm, with farm and irrigation use added on top where it overlaps the peak Source 1: State of Michigan Water Well Manual.

    Required drawdown is peak demand minus what the pump delivers in those seven minutes. A 10-gpm pump in a two-bathroom house produces 70 of the 98 gallons, so 28 must come from the tank.

    And the ceiling on all of it. Arizona states the limit that neither rule contains: a tank cannot compensate for demand greater than your pump or well capacity Source 5: University of Arizona Superfund Research Program, Well Owner's Guide. Storage buys minutes, not gallons per day.

    If the well itself is the constraint, no tank on this page is the answer. The question to ask is about yield, not storage.

    The pre-charge number, and why you will find two of them

    Pre-charge is the air put into the tank before water reaches it. Read it at the air valve, with a tire gauge. Michigan's glossary gives the rule in one sentence: the pressure should be 2 psi less than the cut-in pressure of the pump pressure switch, and a correct pre-charge prevents interruption of water and extends the life of the pump and tank Source 1: State of Michigan Water Well Manual. On a 30/50 switch that is 28 psi.

    You will also find five psi. It is in the same manual. Michigan's sizing chapter writes that if the pre-charge is about 5 psi below the pump cut-in, supplemental supply is obtained from the tank when demand exceeds the pump's capacity Source 1: State of Michigan Water Well Manual. Washington's design manual makes the same figure a standing assumption, taking bladder tanks to be pre-charged about 5 psi below pump-on pressure Source 2: Washington State Water System Design Manual, DOH 331-123.

    The two answer different questions. The placement is the tell. Two psi below cut-in is the normal-operation setting. It keeps the air cushion working at the moment the pump restarts, and it is what you check your own tank against.

    Five psi appears where it appears, inside a supplemental-storage passage and inside a manual's sizing of banks of tanks for a utility. It is a deliberate detune that buys volume at peak and pays in delivered pressure. If you run out mid-shower while the washing machine fills, that trade is on the table. Otherwise 2 psi is your number.

    The same tank, set two ways, is two different tanks

    The instinct when a house runs short at peak is to buy a bigger tank. Michigan's own worked example shows what the settings are worth first. The numbers are larger than most people expect.

    A 120-gallon plain steel tank, run at 30 to 50 psi with no pre-charge, makes about 10 percent of its volume available: 12 gallons. Lower the operating pressure to 20 to 40 psi and pre-charge the tank to 15 psi, and the usable capacity rises to 37.4 gallons, or 31 percent Source 1: State of Michigan Water Well Manual. Same tank, nothing bought, roughly three times the water.

    The cost is real, and belongs in the same breath. 20 to 40 psi delivers less pressure at the shower head than 30 to 50. A household that already finds its pressure weak would be trading the wrong way. That is one reason the settings are a contractor's call.

    Where a second tank is added for storage instead, Michigan's rule is that it is pre-charged lower than the first and the switch differential is set closer together Source 1: State of Michigan Water Well Manual.

    When none of this arithmetic applies

    One system type voids the whole page. Almost nothing written for homeowners says so. Michigan is explicit: conventional pressure tank sizing methodology is not applicable to variable-frequency-drive systems, because the need to achieve a minimum pump run time is not a concern on one, and a much smaller tank can control such a system Source 1: State of Michigan Water Well Manual.

    These are sold to homeowners as constant-pressure systems. If you have one, every run-time figure above is irrelevant to your tank. Following a generic sizing chart buys a tank several times larger than the system needs.

    The manufacturer's installation specification is the authority there. It is the one place on this page where the answer is a document, not a calculation.

    What is yours, and what is not

    Three verdicts, no spectrum. The split on this topic is unusual and worth stating plainly: the arithmetic is entirely yours, and almost none of the physical work is.

    Working out the drawdown your pump needs

    Two numbers and one multiplication, done at a kitchen table with nothing opened and nothing switched. It is also the number a contractor should be sizing against, so having it first turns a recommendation into something you can check.

    DIY-safe

    Reading the cut-in and cut-out pressures off the gauge

    Watching a dial through one cycle. The pair you write down is what every other figure on this page is calculated from.

    DIY-safe

    Checking the pre-charge against the cut-in with a tire gauge

    Only with the pump off at the breaker and the system pressure drained to zero at a tap first, in that order. A pressure tank holds real stored energy, and the air valve is not a place to be guessing at the state of the system. If you are not sure which breaker isolates the pump, that uncertainty is the answer.

    DIY with cautions

    Changing switch settings, re-ranging a system, or fitting a tank

    The pressure switch is a line-voltage device, commonly 240 volts, with contacts that stay live under the cover. Settings and tank are one system rather than two parts: a switch re-ranged without matching the pre-charge to it leaves the original behavior in place at full price.

    What the pro does: Sizes the tank against the pump output and a stated minimum run time rather than against the tank being removed, sets the pre-charge before the tank is filled, and leaves the cut-in, cut-out and pre-charge figures written down.

    Professional only

    What a good quote shows you

    A pressure tank is the one component on a well system most often replaced like for like. A like-for-like swap of a tank that was undersized to begin with reproduces the original problem at full price. Two questions close most of that gap.

    • Ask what pump output and what minimum run time the tank was sized against. Michigan's tables turn on the pump's gallons per minute and a run time, not on the dimensions of the tank being carried out Source 1: State of Michigan Water Well Manual. If the answer is the model number of the old tank, the sizing has not been done. If the answer is a gpm figure and a run time, you can check it against this page in a minute.
    • Ask for the pre-charge, cut-in and cut-out to be set and written on the invoice. Those three numbers are the system and only work as a set: a tank fitted without its pre-charge matched to the switch is a correctly sized tank behaving like a small one. NGWA's guidance applies directly. Ask the contractor for the warranty and maintenance information on individual components, pump and pressure tank included Source 3: National Ground Water Association, Well Owner's Guide 2021. The figures belong in your records.

    Rules, and who is allowed to do the work

    The two manuals cited throughout are Michigan's and Washington's, which are two states' documents rather than national rules. They are used here for pressure system mechanics, which are physics, and not for their permitting requirements, which are local.

    Michigan's Well Construction Code, for instance, requires a pressure tank to sit in an approved pump room, well house, crawl space, basement offset or basement, requires buried tanks to be an approved model, and requires a relief valve where the pump can exceed the tank's working pressure Source 1: State of Michigan Water Well Manual. Its land-division rules ask a well to demonstrate a sustained 10 gallons per minute for four hours, or a combination of yield and storage meeting peak demand, which is rule B's fork written into a rule Source 1: State of Michigan Water Well Manual. Several states license well contractors separately from plumbers. They also restrict wellhead work to that trade.

    Requirements vary by county. Your county health department has the final word on permits, inspections, and what is allowed on your property.

    Opening a system for tank or pump work is also a water-quality event: what to test for and how often covers the retest, and shock chlorination covers disinfection afterwards. More sourced guides are in the guide library.

    Common questions

    What size pressure tank do I need for my well?

    Size it from your pump, not from the tank you are replacing. Michigan's state well manual sets drawdown as the pump's output multiplied by a minimum run time: one minute at 10 to 20 gallons per minute, two at 21 to 50, three at 51 to 75, four at 76 to 100. A 15-gallon-per-minute pump needs 15 gallons of drawdown, which is roughly a 60-gallon nameplate once a bladder tank's 25 percent usable fraction is applied.

    How much air pressure should be in a bladder tank?

    Two psi below the cut-in pressure on the pressure switch, read with the pump off at the breaker and the system drained to zero at a tap first. On a 30/50 switch that is 28 psi. You will also see about five psi below cut-in in print; that is the figure for a tank deliberately asked to supply extra water at peak, bought with a little delivered pressure.

    How long should the pump run to fill the pressure tank?

    At least one full minute for a pump delivering 10 to 20 gallons per minute, and longer for larger pumps, because a bigger motor draws more current on every start. Read it as a specification rather than a symptom: the run time decides how much drawdown the tank must hold.

    How long does a well pressure tank last?

    It depends which kind you have. A plain steel tank is designed to lose air into the water and have it replaced, so it carries an ongoing maintenance task. A bladder or diaphragm tank keeps its air behind a membrane and reaches the end of its life when that membrane fails. Michigan notes that old single-chamber tanks also lose air through pin-hole corrosion.

    Can a well pump run without a pressure tank?

    A conventional fixed-speed pump needs one, or it would restart every time a tap opened. A variable-frequency-drive constant-pressure system is the exception: Michigan states that a large tank is not necessary to make one work, because the minimum-run-time requirement does not apply. Size those from the manufacturer's specification, not from any chart here.

    How much is a pressure tank for a well?

    This page carries no prices on purpose: it specifies the tank rather than buying it. Dated part and installed figures for tanks, switches and pump replacement are in our guide to why a well pump short-cycles, which is also the page to read if your tank is misbehaving rather than being replaced on plan.

    Sources

    1. Michigan Water Well Construction Manual (Chapter 4, water system sizing; Chapter 9, wellhead completion, pumps and pressure tanks). Michigan Department of Environment, Great Lakes, and Energy, Well Construction Programaccessed Jul 2026
    2. Water System Design Manual, DOH 331-123, revised June 2020. A public water system design manual, read here for its definition of withdrawal capacity and its design assumption, not as homeowner guidance. Washington State Department of Health, Office of Drinking Wateraccessed Jul 2026
    3. Well Owner's Guide, 2021 edition (what a pressure tank is for, and when a homeowner should stop and call a professional). National Ground Water Associationaccessed Aug 2026
    4. Well Owner's Guide to Water Supply (the pressurized storage tank's role in a home system). Texas Well Owner Network, Texas A&M AgriLife Extensionaccessed Jul 2026
    5. Well Owner's Guide (the limit of storage against pump and well capacity). University of Arizona Superfund Research Programaccessed Jul 2026